TAA150 OPTIONAL ELECTRIC HEAT DATA
Electric Heat
Size
No.
of
Steps
Volts
Input
kW
Input
1
Btuh
Output
2
Total Unit + Electric Heat
Minimum Circuit
Ampacity
Total Unit + Electric Heat
Maximum Overcurrent
Protection
3 hp 5 hp 3 hp 5 hp
10 kW
1
208 7.5 25,600 40 47 40 50
220 8.4 28,700
1
230 9.2 31,400 44 51 45 60
240 10 34,100
440 8.4 28,700
1
460 9.2 31,400 21 25 25 25
480 10 34,100
550 8.4 28,700
1
575 9.2 31,400 17 20 20 20
600 10 34,100
15 kW
1
208 11.3 38400 53 60 60 60
220 12.6 43,000
1
230 13.5 47,000 59 66 60 70
240 15 51,200
440 12.6 43,000
1
460 13.5 47,,000 29 32 30 35
480 15 51,200
550 12.6 43,000
1
575 13.5 47,000 23 26 25 30
600 15 51,200
25 kW
3
2
208 18.8 64,100 79 86 80 90
220 21 71,700
3
2
230 23 78,300 89 96 90 100
240 25 85,300
440 21 71,700
1
460 23 78,300 44 48 45 50
480 25 85,300
550 21 71,700
1
575 23 78,300 35 38 35 40
600 25 85,300
33.3 kW
3
2
208 25 85,300 100 108 100 110
220 28 95,500
3
2
230 30.6 104,400 114 121 125 125
240 33.3 113,700
440 28 95,500
1
460 30.6 104,400 57 60 60 60
480 33.3 113,700
550 28 95,500
1
575 30.6 104,400 45 48 45 50
600 33.3 113,700
1
Electric heater capacity only − does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
May be used with two stage control (field provided).