DC Inverter Multi VRF System
5
Fig.3
No.
Name Motor Fan blade
Electric box
assembly
Gas pipe valve Liquid pipe valve
2.2 Combinations of Indoor and Outdoor Units
(1) See below the number of indoor units that can be connected to the outdoor unit.
(2) The total capacity of indoor units should be within 50%~135% of that of the outdoor unit.
Model
Max sets of connectable IDUs
VEP034N432US
5
VEP042N432US
6
VEP048N432US
8
VEP042N432U
7
VEP048N432U
8
VEP060N432U
9
(3) Can be connected to various indoor units. When any one of the indoor units receives
operating command, outdoor unit will start operation as per required capacity. When all
indoor units stop, outdoor unit will be shut off.
2.3 Operating Range
Cooling
Outdoor temperature: -5
°C
~52
°C
Heating
Outdoor temperature: -20
°C
~27
°C
VEP048N432US