The Lennox VE High ESP Fan Coil is an indoor unit designed for VRF (Variable Refrigerant Flow) systems, offering a range of models and configurations to suit various installation needs. This manual provides comprehensive instructions for its installation, operation, and maintenance.
Function Description:
The VE High ESP Fan Coil is a key component of a VRF air conditioning system, responsible for delivering conditioned air to indoor spaces. It operates in multiple modes including cooling, heating, fan-only, and dehumidifying, providing flexible climate control. The unit is designed for concealed ceiling installation, with options for various air duct configurations to distribute air effectively. It integrates with a wired controller (VEWCL1B, standard) and can optionally be controlled by a remote controller (VERCL1A). Key functions include fan speed adjustment, temperature adjustment, X-fan function (to prevent mold growth by drying the evaporator coil), quiet function, sleep function, save function, memory function, absence function, timer function, low-temperature dehumidify function, filter cleaning reminding function, I Feel function (for enhanced comfort based on remote sensor readings), light function, and swing function (for air direction control).
Important Technical Specifications:
The manual details various models, including VEHD019N432U, VEHD021N432U, VEHD024N432U, VEHD027N432U, VEHD031N432U, VEHD034N432U, VEHD038N432U, VEHD043N432U, VEHD048N432U, and VEHD055N432U. These models vary in cooling capacity (MBtu/h), with specific dimensions provided for different capacity ranges (e.g., 5.6kW to 14.0kW and 16kW).
Voltage Ratings:
The units support various voltage ratings:
- K: 230/60/3 and 220/50/3
- N: 380V/50-60Hz/3Ph
- G: 460V/60Hz/3Ph
- Y: 230V/60Hz/3Ph
- T: 220V/50Hz/1Ph
- P: 230V/60Hz/1Ph
- U: 220V/50-60Hz/1Ph
Refrigerant: The system uses R410a refrigerant.
Rated Working Conditions:
- Indoor Side:
- Cooling: Dry Bulb Temp 27°C (80.6°F), Wet Bulb Temp 19°C (66.2°F)
- Heating: Dry Bulb Temp 20°C (68.0°F), Wet Bulb Temp 15°C (59.0°F)
- Working Temperature Range: 16°C to 32°C
- Outdoor Side:
- Cooling: Dry Bulb Temp 35°C (95°F), Wet Bulb Temp 24°C (75.2°F)
- Heating: Dry Bulb Temp 7°C (44.6°F), Wet Bulb Temp 6°C (42.8°F)
Power Cord and Air Switch Capacity:
For models like VEHD019N432U to VEHD055N432U (220~240V-1ph-50Hz or 208~230V-1ph-60Hz), the recommended air switch capacity is 6A, with a minimum sectional area of 1.0 mm² for both the ground wire and power cord. Copper wire only is specified for power cords, and if the cord length exceeds 15m (49-1/4 feet), the sectional area should be increased.
Refrigerant Pipe Connection Torque:
- 9.52mm (3/8 inch): 35-40 N·m
- 15.9mm (5/8 inch): 60-65 N·m
- 19.04mm (3/4 inch): 70-75 N·m
Drainage Pipe Installation: The drainage pipe should have a downward gradient of at least 1%~2% to ensure smooth condensation water drainage. The raising pipe for drainage should be lower than 850mm (31-1/2 inches).
Communication Line: Shielded twisted pair lines are recommended for communication between indoor units and wired controllers, and between indoor units and outdoor units, especially in environments with strong electromagnetic interference. The total length of communication cable for wired controllers should not exceed 250m (850 feet), and for indoor-outdoor unit communication, it can reach up to 1000m (3280 feet), or 1500m (4920 feet) if the wire diameter is enlarged to 18AWG.
Usage Features:
- Installation Flexibility: The unit is designed for concealed ceiling installation, with detailed instructions for drilling bolt holes, installing hanger bolts, and connecting refrigerant and drainage pipes. It provides specific dimensions for air outlet and air-return openings for different models.
- Wired and Remote Control: The unit can be controlled by a standard wired controller (VEWCL1B) or an optional remote controller (VERCL1A). Up to two wired controllers can be connected to one indoor unit (master/slave configuration), and one wired controller can manage up to 16 indoor units.
- Safety Precautions: The manual emphasizes critical safety measures, including proper earthing, using exclusive accessories, ensuring correct power supply, ventilating during refrigerant leakage, and not attempting self-repair. It also warns against inserting objects into air grilles and operating the unit with wet hands.
- Preheating: For optimal reliability, the unit consumes a small amount of power in standby mode for communication and refrigerant preheating. If the unit is not used for a long time, the power should be cut off, but preheating is recommended before subsequent operation.
- Temperature Control: Under cooling mode, users are advised not to set the room temperature too low and to maintain a temperature difference of no more than 5°C between indoor and outdoor units.
- Troubleshooting: A comprehensive table of error codes (LO-L9, LA-LH, d1-dE, db) is provided to assist in diagnosing common issues. Basic troubleshooting steps are also outlined for problems like the unit not starting, stopping after a while, or experiencing poor cooling/heating effects.
Maintenance Features:
- Filter Cleaning: Filters should be removed from the inlet of the indoor unit and cleaned regularly (usually every two weeks in dusty environments). Dust can be removed with a vacuum cleaner, or dirty filters can be washed with warm water and mild detergent and dried in the shade. It is crucial not to dry filters by fire to prevent deformation or fire.
- Seasonal Maintenance (Before Use): Before seasonal use, checks should include ensuring air inlet/outlet are not blocked, verifying secure grounding, confirming all power and communication cables are connected, and checking for any error codes.
- Seasonal Maintenance (After Use): After seasonal use, the unit should be set to fan mode for half a day on a sunny day to dry its inner parts. For long periods of non-use, the power supply should be cut off to save energy, which will also clear the wired controller screen.
- Professional Service: The manual strongly advises against user-performed repairs due to the risk of electric shock or fire. In case of malfunctions or abnormal situations (e.g., burning smell), users should immediately power off the unit, cut off the main power supply, and contact a Lennox-appointed service center.
- Drainage System Test: After electrical work, the drainage system must be tested by injecting approximately 1L of purified water into the drain pan and verifying proper drainage through the drain socket. This test should be performed before ceiling decoration.
The Lennox VE High ESP Fan Coil is designed for efficient and reliable climate control, with detailed instructions to ensure safe installation, optimal performance, and ease of maintenance.