Statement 20:
CAUTION:
To avoid personal injury, before lifting the unit, remove all the blades to reduce
the weight.
Statement 21:
CAUTION:
Hazardous energy is present when the blade is connected to the power source.
Always replace the blade cover before installing the blade.
Statement 22:
CAUTION:
To reduce the risk of electric shock or energy hazards:
v This equipment must be installed by trained service personnel in a
restricted-access location, as defined by the NEC and IEC 60950, Third Edition,
The Standard for Safety of Information Technology Equipment.
v Connect the equipment to a reliably grounded safety extra low voltage (SELV)
source. An SELV source is a secondary circuit that is designed so that normal
and single fault conditions do not cause the voltages to exceed a safe level (60
V direct current).
v The branch circuit overcurrent protection must be rated at a minimum of 13 A
to a maximum of 15 A.
v Use 16 American Wire Gauge (AWG) or 1.3 mm
2
copper conductor only, not
exceeding 3 meters in length.
v Torque the wiring-terminal screws to 12 inch-pounds (1.4 newton-meters).
v Incorporate a readily available approved and rated disconnect device in the
field wiring.
Chapter 1. English 1-9