The input voltage drops to the Turn-Off voltage
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F019A: PS1_THERMAL_ERR: Power Supply, Power Supply Failure detected was asserted.
The temperature sensing device internal to the power supply reports the warning temperature is reached
and persists over 30 seconds
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F019B: PS2_THERMAL_ERR: Power Supply, Power Supply Failure detected was asserted.
The temperature sensing device internal to the power supply reports the warning temperature is reached
and persists over 30 seconds
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F019C: PS1_FAN_ERROR: Power Supply, Power Supply Failure detected was asserted.
The power supply is not possible to maintain a fan speed sufficient to provide necessary cooling for the
power supply
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F019D: PS2_FAN_ERROR: Power Supply, Power Supply Failure detected was asserted.
The power supply is not possible to maintain a fan speed sufficient to provide necessary cooling for the
power supply
Severity: Critical
User Action:
Chapter 2. SMM2 events 19