1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F01A0: PS1_OVS_ERROR: Power Supply, Power Supply Failure detected was asserted.
The power supply shutdown due to throttle# assertion over 3 seconds for indicating a load over 105% of
the power supply rating
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F01A1: PS2_OVS_ERROR: Power Supply, Power Supply Failure detected was asserted.
The power supply shutdown due to throttle# assertion over 3 seconds for indicating a load over 105% of
the power supply rating
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F01A6: PS1_VIN_UVI_ERR: Power Supply, Power Supply Failure detected was asserted.
The input power applied does not exceed the Turn-On voltage
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F01A7: PS2_VIN_UVI_ERR: Power Supply, Power Supply Failure detected was asserted.
The input power applied does not exceed the Turn-On voltage
Severity: Critical
User Action:
1. Check power supply LEDs
If AC LED is not lit, check power cord and input voltage.
If DC LED is not lit, remove and reinstall power supply.
If error LED is lit, replace the power supply.
2. If fault recurs, please call service.
086F01AC: PS1_INTRL_OC_ERR: Power Supply, Power Supply Failure detected was asserted.
20
ThinkSystem D2 Enclosure, Modular Enclosure, Modular Enclosure for 6U Configuration and ThinkSystem SD530 Compute Node
Messages and Codes Reference