– memory speed or link disable setting changed
– UPI speed or link disable setting changed
– C1E, C-state, or P-state setting changed
– # of enabled CPU cores changed
– Turbo setting changed
– CPU freq limit changed
2. If the error recurs, replace the node
• 216F0076: NODE3_PMIN_2_BIG: Slot Or Connector, Fault Status asserted was asserted.
The inventory power reports from BMC includes invalid value, whose PMin is greater then Pmax
Severity: Critical
User Action:
1. Changing items in UEFI F1 Setup to force PTU running again
– device is enabled / disabled
– memory speed or link disable setting changed
– UPI speed or link disable setting changed
– C1E, C-state, or P-state setting changed
– # of enabled CPU cores changed
– Turbo setting changed
– CPU freq limit changed
2. If the error recurs, replace the node
• 216F0077: NODE4_PMIN_2_BIG: Slot Or Connector, Fault Status asserted was asserted.
The inventory power reports from BMC includes invalid value, whose PMin is greater then Pmax
Severity: Critical
User Action:
1. Changing items in UEFI F1 Setup to force PTU running again
– device is enabled / disabled
– memory speed or link disable setting changed
– UPI speed or link disable setting changed
– C1E, C-state, or P-state setting changed
– # of enabled CPU cores changed
– Turbo setting changed
– CPU freq limit changed
2. If the error recurs, replace the node
• 256F0138: EIOM_NO_PRESENCE: Entity Presence, Entity Absent was asserted.
A event indicate SMM No EIOM card existence
Severity: Critical
User Action:
Insert the EIOM card
• 2B6F0139: PRIMRY_BOOT_FAIL: Version Change, Firmware or software change detected with
associated Entity was asserted.
A event indicate booting from bank 2
Severity: Warning
User Action:
Service support
Chapter 2. SMM2 events 35