3. If the error recurs, replace the node
• 216F0061: NODE2_XCC_FAULT: Slot Or Connector, Fault Status asserted was asserted.
The BMC fail to start the initialisation in 2 minutes since the compute node inserted.
Severity: Critical
User Action:
1. Reset XCC
2. If the error recurs, reseat the node
3. If the error recurs, replace the node
• 216F0062: NODE3_XCC_FAULT: Slot Or Connector, Fault Status asserted was asserted.
The BMC fail to start the initialisation in 2 minutes since the compute node inserted.
Severity: Critical
User Action:
1. Reset XCC
2. If the error recurs, reseat the node
3. If the error recurs, replace the node
• 216F0063: NODE4_XCC_FAULT: Slot Or Connector, Fault Status asserted was asserted.
The BMC fail to start the initialisation in 2 minutes since the compute node inserted.
Severity: Critical
User Action:
1. Reset XCC
2. If the error recurs, reseat the node
3. If the error recurs, replace the node
• 216F0074: NODE1_PMIN_2_BIG: Slot Or Connector, Fault Status asserted was asserted.
The inventory power reports from BMC includes invalid value, whose PMin is greater then Pmax
Severity: Critical
User Action:
1. Changing items in UEFI F1 Setup to force PTU running again
– device is enabled / disabled
– memory speed or link disable setting changed
– UPI speed or link disable setting changed
– C1E, C-state, or P-state setting changed
– # of enabled CPU cores changed
– Turbo setting changed
– CPU freq limit changed
2. If the error recurs, replace the node
• 216F0075: NODE2_PMIN_2_BIG: Slot Or Connector, Fault Status asserted was asserted.
The inventory power reports from BMC includes invalid value, whose PMin is greater then Pmax
Severity: Critical
User Action:
1. Changing items in UEFI F1 Setup to force PTU running again
– device is enabled / disabled
34
ThinkSystem D2 Enclosure, Modular Enclosure, Modular Enclosure for 6U Configuration and ThinkSystem SD530 Compute Node
Messages and Codes Reference