32 SF01U
NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.
NO. PARAMETER NAME RANGE OF ADJUSTMENT
FACTORY
DEFAULT
(NOTE 1)
31-37 PRESET SPEEDS 0.0 - MAXIMUM FREQUENCY 0.0 Hz
38 SKIP BANDWIDTH 0.0 - 10.0 Hz 0.0 Hz
39 SPEED SCALING 0.0 - 6500.0 0.0
40 FREQUENCY SCALING 3.0 - 2000.0 Hz 60.0 Hz
41 LOAD SCALING 10 - 200 % 200 %
42 ACCEL/DECEL #2 0.1 - 3600.0 SEC 20.0 SEC
43 SERIAL ADDRESS 1 - 247 1
44 PASSWORD 000 - 999 225
47 CLEAR HISTORY MAINTAIN (01), CLEAR (02) MAINTAIN (01)
48 PROGRAM SELECTION
USER SETTINGS (01), OEM SETTINGS (02),
RESET OEM (03), RESET 60 (04),
RESET 50 (05), TRANSLATE (06)
USER
SETTINGS (01)
50 FAULT HISTORY (VIEW-ONLY) (N/A)
51 SOFTWARE CODE (VIEW-ONLY) (N/A)
52 DC BUS VOLTAGE (VIEW-ONLY) (N/A)
53 MOTOR VOLTAGE (VIEW-ONLY) (N/A)
54 LOAD (VIEW-ONLY) (N/A)
55 0-10 VDC INPUT (VIEW-ONLY) (N/A)
56 4-20 mA INPUT (VIEW-ONLY) (N/A)
57 TB STRIP STATUS (VIEW-ONLY) (N/A)
58 KEYPAD STATUS (VIEW-ONLY) (N/A)
59 TB-30 OUTPUT (VIEW-ONLY) (N/A)
60 TB-31 OUTPUT (VIEW-ONLY) (N/A)