Code table
10
Function library
10.20
L
10.20-39
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0421*
v
Free configuration
analog process
data output words
Output of analog signals on bus
^
10.12-10
1 AIF-OUT.W1 8
Operation with process controller (C0238 = 0, 1):
Act. process controller value (PCTRL1-ACT)
Operation without process controller (C0238 = 2):
Output frequency without slip (MCTRL1-NOUT)
2 AIF-OUT.W2 0 Output frequency (MCTRL1-NOUT+SLIP)
3 CAN-OUT1.W1 /
FIF-OUT.W1
255 Not assigned (FIXED-FREE) With Lenze setting, CAN-OUT1.W1
and FIF -OUT.W1 are defined as d igital
outputs and the 16-bit controller
status word 1 (C0417) is assigned to
them.
Before you assign an analog signal
source (C0421/3
255), th e digital
assignment must be deleted
(C0417/x = 255)! Oth erwise the
output signal would be incorrect.
4 CAN-OUT1.W2 /
FIF-OUT.W2
255 Not assigned (FIXED-FREE)
5 CAN-OUT1.W3 /
FIF-OUT.W3
255 Not assigned (FIXED-FREE)
6 CAN-OUT1.W4 /
FIF-OUT.W4
255 Not assigned (FIXED-FREE)
7 CAN-OUT2.W1 255 Not assigned (FIXED-FREE)
8 CAN-OUT2.W2 255 Not assigned (FIXED-FREE)
9 CAN-OUT2.W3 255 Not assigned (FIXED-FREE)
10 CAN-OUT2.W4 255 Not assigned (FIXED-FREE)
C0421* Possible analog sig nals for C0421 ^
v
t
0 Output frequency (MCTRL1-NOUT+SLIP) 24000 480 Hz
10.12-10
(cont.)
1
Device utilisation (MCTRL1-MOUT) at V/f
characteristic control (C0014 = 2 or 3)
16383 Rated active inverter current
(active current/C0091)
Actual motor torque (MCTRL1-MACT) at vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)
16383 Rated motor torque
2 Apparent motor current (MCTRL1-IMOT) 16383 Rated inverter current
3 DC-bus voltage (MCTRL1-DCVOLT) 16383 565 VDC at 400 V mains
16383
325 VDC at 230 V mains
4 Motor power 285 Rated motor power
5 Motor voltage (MCTRL1-VOLT) 16383 Rated motor voltage
6 1/output frequency (1/C0050) (MCTRL1-1/NOUT) 195 0.5 × C0011
7 Output frequency with limits
C
C
C
24000 480 Hz
p
q
y
(DCTRL1-C0010...C0011)
0
f < C0010
24000
(f C0010)
480 Hz
f C0010
8
Operation with process controller (C0238 = 0, 1):
Act. process controller value (PCTRL1-ACT)
24000 480 Hz
Operation without process controller (C0238 = 2):
Output frequency without slip (MCTRL1-NOUT)
Show/Hide Bookmarks