Technical data
General data and operating conditions
4

45
EDKRBD180R DE/EN/FR 6.0
Mounting conditions
Mounting location
l The mounting location must comply with the
device features mentioned in the chapter "General
data".
l Flammable materials or substances may not be
placed in the vicinity of the brake resistor.
l The heat generated by the brake resistor must be
dissipated freely.
Mounting position Vertically suspended with connecting cables at the
bottom.
Free space
at the top > 200 mm
at the bottom > 100 mm
to the sides > 25 mm