0 Not active
0 9600 bps (or 9600,8,N,2 if C01= 8...11)
1 Inhibit
0 TRIP reset by LOW - signal at terminal
28 or mains switching or HIGH signal at
the digital input “TRIP reset”
0 Start after LOW-HIGH change at
terminal 28
0 None
- 7 -
smd series
Parameter Setting
c06c06
c06c06
c06
0.0
c20c20
c20c20
c20
100
c40c40
c40c40
c40
0.0
c42c42
c42c42
c42
1
c61c61
c61c61
c61
c62c62
c62c62
c62
c63c63
c63c63
c63
c70c70
c70c70
c70
0
c71c71
c71c71
c71
0.0
c78c78
c78c78
c78
c79c79
c79c79
c79
L
Holding time - automatic
DC injection brake (Auto-
DCB)
I
2
t switch-off (thermal
motor monitoring)
Frequency setpoint via
keys or Modbus
Start condition (with
mains on)
Present
Last
Last but one
Configuration TRIP reset
(error reset)
Auto TRIP reset delay
Operating time counter
Mains connection time
counter
Automatic motor braking below 0.1 Hz by means of
motor DC current for the entire holding time
(afterwards: U, V, W inhibited)
9990.0 {s}
10030 {s}
2400.0 {Hz}
60.00.0 {s}
1 Auto start if terminal 28 = HIGH
1 Auto-TRIP reset
status/error message
error message
Display
Total time in status “Start”
Display
Total time of mains = on
c08c08
c08c08
c08
100.0Analog output scaling When 10 VDC is output at terminal 62, it will equal
this value (see c11)
9990.0
2 Output frequency 2-10 VDC
1 Output frequency 0-10 VDC
c11c11
c11c11
c11
0Configuration - analog
output (62)
5 Dynamic Braking
3 Load 0-10 VDC
4 Load 2-10 VDC
Code Possible Settings IMPORTANT
No. LenzeName Selection
c17c17
c17c17
c17
0Configuration - digital
output (A1)
Output is energized if
0 Ready
1 Fault
2 Motor is running
3 Motor is running - CW rotation
4 Motor is running - CCW rotation
5 Output frequency = 0 Hz
6 Frequency setpoint reached
7 Threshold (C17) exceeded
8 Current limit (motor or generator mode)
reached
100% = smd rated output current
2 2400 bps (or 9600,8,E,1 if C01= 8...11)
1 4800 bps (or 9600,8,N,2 if C01= 8...11)
c25c25
c25c25
c25
0LECOM baud rate
3 1200 bps (or 9600,8,O,1 if C01= 8...11)
0 Quick stop
n20n20
n20n20
n20
0LECOM power up state
2 Quick stop
1 Controller inhibit
n22n22
n22n22
n22
0Serial time-out action
3 Trip fault “FC3”
n23n23
n23n23
n23
50
Serial fault time
6553550 {ms}
Auto-TRIP reset after the time set in c71
Caution: Maximum setting is rated motor current
(see nameplate)
Does not provide full motor protection!
Only active if C01 is set properly
Display
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
Use c08 to scale signal
If C01 = 8...11, Modbus serial communications is
active
Selects controller reaction to serial timeout
Sets the serial timeout length
0.0 = not active
999 = continuous brake
C99C99
C99C99
C99
Software version Display, format x.yz