Wiring the device modules
Communication modules
8
67
EDK94ASH24 ZH/EN 4.1
PROFIBUS
E94YCPM001A
Fig. 8−4 E94AYCPM communication module (PROFIBUS)
Connections
Pos. Description
X200 External supply of the communication module
Design: Plug connector with screw connection, 2−pole
X201 Connection for PROFIBUS
Design: Sub−D socket, 9−pole
X200 Labelling Description
+
-
24 V external supply via a safely separated power supply unit (SELV/PELV)
+ 24VDC
20.4 − 0% ... 28.8 V+ 0%, max. 200 mA
SSP94KP200
GND
Reference potential
View Pin Designation Explanation
1
2
3
4
5
6
7
8
9
1 free
2 free
3 RxD/TxD−P Data line B (received data/transmitted data plus)
4 RTS Request To Send (received data/transmitted data, no differential
signal)
5 M5V2 Data ground (ground to 5V)
6 P5V2 5 V DC / 30 mA (bus termination)
7 free
8 RxD/TxD−N Data line A (received data/transmitted data minus)
9 free