6 Electrical installation
Im portant notes
6.1 Im portant notes
Hazardous voltage on the power connections even when disconnected
from mains: residual voltage >60 V!
Before w orking on the power connections, always disconnect the drive
com ponent from the mains and w ait until the m otor is at standstill.
Verify safe isolation from supply!
@ Stop!
Electrical connections must be carried out in accordance w ith the
national and regional regulations!
Observe tolerances according to IEC/EN 60034-1:
-V o lta g e ±5 %
- Frequency ±2 %
- W ave form , sym m etry (increases heating and affects electrom agnetic
com patibility)
Observe notes on w iring, inform ation on the nam eplate, and the connection scheme in
the term inal box.
The connection m ust ensure a continuous and safe electrical supply, i.e.
- no loose w ire ends,
- use assigned cable end fittings,
- ensure good electrical conductivity o f the contact (remove residual lacquer) if an
(additional) PE connection on the m otor housing is used),
- establish a safe PE conductor connection,
-tig h te n the plugin connector to the lim it stop.
-A f te r the connection is com pleted, make sure th at all connections on the
term inal board are firm ly tightened.
The sm allest air gaps between uncoated, live parts and against earth must not fall
below the fo llow in g values.
Minimum requirements for basic
insulation according to IEC/EN
60664-1 (CE)
Higher requirements for UL
design
Motor diameter
3.87 mm
6.4 mm < 178 mm
9.5 mm > 178 mm
The term inal box has to be free of foreign bodies, dirt, and hum idity.
All unused cable entries and the box itself m ust be sealed against dust and water.
28
Lenze BA 33.0006 3.0