Max. total rated mains currents at 40 °C
Cable installaon in compli-
ance with
UL 61800-5-1
Laying system
cable cross‐secon AWG 16 14
I
N1
+ L
N2
+ I
N3
+ I
Nn
A 8.0 12.0
Fuse
Characteriscs
Typ. rated current A --- ---
Max. rated current A 10 15
Circuit breaker
Characteriscs
Typ. rated current A --- ---
Max. rated current A 10 15
Motor connecon
X3 mains connecon with QUICKON connector
Pin assignment
Con-
tact
Name Meaning
1 L1 Mains connecon Phase L1
2 L2 Mains connecon Phase L2
3 L3 Mains connecon Phase L3
4 PE PE conductor
Control connecon X1 with M12 connector, A-coded, pins
Pin assignment
Con-
tact
Name Meaning
1 n.c.
2 DI2 Digital input 2
3 GND-I Earth of digital inputs
4 DI1 Digital input 1
Control connecon X2 with M12 connector, A-coded, pins
Pin assignment
Con-
tact
Name Meaning
1 24 V 24 V-supply (DO1 supply)
2 DI3 Digital input 3 (reference X1;3 = GND-I)
3 GND-O Earth of digital outputs
4 DO1 Digital output 1
Electrical installaon
Mains connecon
66