Technical data
Standards and operang condions
Conformies/approvals
Conformity
  CE 2014/35/EU Low-Voltage Direcve
   
2014/30/EU EMC Direcve (reference: CE-typical drive system)
  EAC TR TC 004/2011 Eurasian conformity: safety of low voltage equipment
   
TP TC 020/2011 Eurasian conformity: electromagnec compability of tech-
nical means
Approval
  CCC   GB Standard 12350-2009
 
cULus UL 61800-5-1 for USA and Canada (requirements of the CSA 22.2 No. 14)
Industrial Control Equipment, Lenze File No. E132659
Protecon of persons and device protecon
Enclosure
  IP55 EN 60529  
 
Type 4 indoor only
Type 12
NEMA 250  
Insulaon resistance
  Overvoltage category III EN 61800-5-1 Site altude 0 … 2000 m above sea level
 
Overvoltage category II EN 61800-5-1 Site altude more than 2000 m above sea level:
External measures for compliance with overvoltage cate-
gory II are necessary, e.g. connecon of an isolang trans-
former upstream , connecon of an overvoltage protecon
device upstream
Protecve insulaon of control circuits
  Safe separaon from the mains supply by
means of double/increased insulaon for
digital inputs and outputs
EN 61800-5-1 Site altude 0 … 2000 m above sea level
 
Upstream connecon of overvoltage pro-
tecon device
EN 61800-5-1 Site altude more than 2000 m above sea level:
Addional external separang measures necessary for pur-
poses of safe separaon.
Protecve measures against
  Short circuit EN 61800−5−1 To a limited extent, fault acknowledgement necessary
 
earth fault EN 61800−5−1 To a limited extent, fault acknowledgement necessary
 
Overvoltage   Yes
 
Motor stalling   Yes
 
Motor overtemperature  
I
2
 xt-monitoring
Leakage current
  > 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
 
Equipotenal bonding   Addional M5 thread with terminal at the terminal box for
connecng another PE cable (up to max. 6 mm
2
 )
Total fault current
  Residual current operated switch 30 mA,
Type B
  In TN power supply systems
Cyclic mains switching
  3 mes a minute, max. 20 mes per hour   Mains switching 3 mes in one minute must be followed by
a pause of 9 minutes.
Starng current
  5.6 A mains power-on current    
Technical data
Standards and operang condions
Conformies/approvals
78