Leviton Load Center
First Time User Guide
Thank you for choosing the Leviton Load Center!
This First Time User Guide oers tips and support.
•
Order the covers separately; clear doors are a popular
option for indoor applications.
•
Each Load Center ships with a standard Panel Schedule. Window
Doors/Covers include an alternate Panel Schedule that is compatible
with the door design. Additionally, Panel Schedules for all Indoor panel
sizes and door types can be purchased in bulk packs, and are available
as a .PDF download on Leviton.com.
•
A temporary circuit directory is supplied on the Paint Shield (Figure 1).
•
Neutral wires must terminate at the circuit breaker for all smart
and safety breakers (AF, GF, EP, Dual). However, it is the preferred
method for all circuits.
•
For 2-pole breakers that are 60A or lower, the Neutral wire must be
installed in-between the two phase wires where the “N” is denoted
on the breaker (Figure 2). For 2-Pole breakers greater than 60A, the
Neutral wire must go to the Neutral bar (Figure 3).
•
All non-electronic 2-Pole breakers, as well as -G breakers operate at
both 120/240V and 120/208V.
•
A Leviton Surge Protective Breaker can be installed in any breaker
location to provide whole-panel surge protection, as well as visual
indication of protection status. It also provides overcurrent protection
for the spaces/circuits it inhabits.
Figure 1:
30 Space Paint Shield
Figure 2:
2-pole breaker with “N” denoted to
show where to install the neutral wire