User Manual for BFS-i06
www.levitronix.com
PL-3502-00, Rev04, DCO# 24-054
This document and its content is confidential and the property of Levitronix
®
and shall not be reproduced, distributed,
disclosed or used for manufacturing or sale of Levitronix
®
products without the expressed written consent of Levitronix
®
.
5.2 Operation for ATEX / IECEx Application
Specific precautions may be considered while using the bearingless fan in potentially explosive gas
atmospheres according to ATEX / IECEx category 2G/2D (Zone 1 and 21) or 3G/3D (Zone 2 and 22).
Operational Temperature 85°C T6
Maximum allowed gas temperature is 40°C / 104°F for the use in Ex classified
applications.
Protection against Objects
(IP20).
50 mm (IP10).
If installed in a duct system, protection may be anywhere upstream (inlet) or
downstream (outlet).
Do not operate the fan against closed valves
Operation against closed valves might lead to increased gas temperature.