Trouble Shooting
15
Water pipe overheated
Code
No.
Description Cause Normal Condition
Abnormal operation of
electric heater
Leaving water temperature
is above 72°C
If there is no problem in electric heater
control, possible maximum leaving
water temperature is 62°C.
Start
END
(it is normal
condition)
A
A
B
B
NO
YES
YES
YES
YES
NO
NO
Leaving
water temperature is
higher than target
water temperature
Thermostat
is installed
Leaving
water temperature is
higher than 62 °C
This is unexpected case.
Turn off the system and call service center.
If the system is not turned off before it yields
error code (CH15), very hot leaving water will
be generated and it is harmful to human.
Room air is not fully heated by under floor
heating.
Wait while room air is heated by target
temperature of thermostat.