18 | ART COOL
TM
MULTI V Wall-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Electrical Data
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of a fuse, use the circuit breaker.
Model Number
Voltage
Range
MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
SE Frames
ARNU073SER2
187-253
0.29
15
0.3
60 208-230V 1
40 40
ARNU093SER2 0.29 0.3 40 40
ARNU123SER2 0.29 0.3 40 40
ARNU153SER2 0.29 0.3 40 40
S8 Frames
ARNU183S8R2
187-253
0.29
15
0.3
60 208-230V 1
35 35
ARNU243S8R2 0.29 0.3 35 35
Table 12: Art Cool Mirror Wall-Mounted Indoor Unit Electrical Data.