General Drain Piping Information
All wall-mounted indoor units generate water during cooling
operation, therefore, properly handling this condensation must be
considered. Wall-mounted indoor units apply the gravity drain meth-
od, but a field-supplied condensate pump can be installed (optional,
sold separately). Depending on the location of the indoor unit, con-
densation can be drained directly to the outside of the building, or a
common indoor unit drainage piping system can be installed.
Drain Hose
Wall-mounted indoor units have a built-in drain hose. If necessary,
the drain hose can be extended.
Drain Piping
Drain piping must have down slope (1/50 to 1/100).
Any holes through the ceilings, walls, etc., must be large enough to
accommodate the drain piping and insulation.
To prevent reversal flow, do not provide up and down slope.
Do not exert extra force on the drain port on the indoor unit during
drain piping connection.
Indoor Unit Drain Type
Drain Pipe Diameter
(ID, in.)
SE Frame Art Cool Wall-Mounted
Gravity
Ø5/8
S8 Frame Art Cool Wall-Mounted
SB Frame Standard Wall-Mounted
Ø1
SC Frame Standard Wall-Mounted
Table 34: Indoor Unit Drain Piping Specications.
Drain pan
Insulation
Drain hose
Insulation
Figure 36: Installation Plates.
Figure 37: Diagram of an Indoor Unit with a Gravity Drain.
26-5/8
12-7/8
16-5/8
10-7/16
2-13/16
Unit: inches
SB Frame Standard Wall-Mounted Indoor Unit
2-13/16
2-3/4
2-1/4
Right rear
piping
Left rear
piping
Installation Plate
Measuring Tape
Measuring Tape
Hanger
Place a level on raised tab
Unit Outline
8-3/16
4-3/16
18-1/8 22-1/2
2-13/16
Unit: inches
SC Frame Standard Wall-Mounted Indoor Unit
S8 Frame Art Cool Wall-Mounted Indoor Unit
Left rear piping Right rear piping
2-3/4 inch
5-1/4 inch
2-3/4 inch
3-15/16 inch
2-3/4 inch
4-5/16 inch
2-3/4 inch
4-5/16 inch
2-9/16 inch
3-3/8 inch
Left rear piping Right rear piping
SE Frame Art Cool Wall-Mounted Indoor Unit
Figure 38: Drain Piping Slope.