Part 2 Functions & Controls
5.8 Overheating Protection (Power Module)
If the temperature of the heat sink thermistor. reaches over Toff, the Compressor stop instantly.
The compressor operating frequency is limited according to the heat sink thermistor. (refer to below FIG.)
It will blink 4 times, when the thermistor is open or short, also when the temperature is over T off.
5.9 Total Current Control (Over Current Protection)
5.9.1 CT1 control
If the operating current reaches I1, the operating frequency of the compressor decreases.
After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuously, the
operating frequency of compressor increases by 1step.
5.9.2 CT2 control
If the operating current of the appliance reaches I2, the compressor stop instantly and two minutes later the compres-
sor restarts again.
If CT2 occurs 5 times within one hour, the appliance turn off and displays ERROR CODE 7.
T off °C
T2 °C
Heat Sink Temp.
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
T = (T off - T on)
T1 = T on + T
T2 = T on + 2
*
T
- I1 :Current of operating frequency down(5.5A ~ 12.0A)
- I2 : Current of compressor cut off(9.0A ~ 14.0A)
* ( I1, I2 depends on model )
T on : 85°C (Model by Model)
T off : 95 ~ 105°C (Model by Model)
NOTE: Some Models are different by Ton, and Toff.