Part 2 Functions & Controls
5.10 DC Peak control
5.10.1 DC Peak Current Error by a fault signal of IPM
If the operating current of IPM reaches 35A 3A, the compressor stops instantly.
If DC PEAK occurs 5 times within 1 hour, the appliance turns off and displays ERROR CODE 6.
5.10.2 DC Peak Current Error by the compressor lock
If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance
turns off and display ERROR CODE 6.
5.10.3 DC Peak Current Error by the Outdoor Fan Lock
If this problem occurs 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65 C while the com-
pressor is operating, the appliance turns off and displays ERROR CODE 6.
5.11 Discharge Pipe Temp Control
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor stops
instantly.
The compressor operating frequency is limited according to the compressor dome TH. (Refer to below Fig.)
Temperature range of COMP SPEC varies by 10°C.
T1 : 95 ~ 100°C ( Model by model )
T2 : 105 ~ 110°C ( Model by model )
D-Pipe Temp.
COMP Freq. Free Free
Fh min
OFFFc-1 Fc-1Fc-2 Fc-2
T = (T off - T2)/2
T1 = T2 - 2
*
T
T3 = T2 + T
T off °C
T2 °C
T3 °C
T1 °C
-13 °C
NOTE: Some Models are different by T1, and T2.