INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
www.lghvac.com
www.lg.com
Copyright © 2021 LG Electronics Inc. All Rights Reserved.
ENGLISH
SPLIT ROOFTOP UNIT(RTU)
MFL71810404
Rev.00

Questions and Answers

  • K
    Kayla JohnsonAug 10, 2025
    Does LG Control Unit economizer save program values after power loss?
    • A
      Anna CarterAug 10, 2025
      Once changes are stored in the LG Control Unit's controller, they will be saved until the operator changes them, even if the unit loses power.
  • K
    Keith FrancisAug 15, 2025
    How long does LG Control Unit stay in checkout mode?
    • F
      fwalkerAug 15, 2025
      If the LG Control Unit is left in checkout mode, it will remain in this mode for 10 minutes without any input, after which it will return to normal operation.
  • J
    Joe JohnsonAug 19, 2025
    What to do if LG Control Unit outdoor damper closes when commanded to open?
    • H
      Hannah SotoAug 19, 2025
      Check the actuator linkage or rotation of the LG Control Unit. In CHECKOUT mode, the outdoor damper should drive open to closed, with the return air damper having the opposite effect.
  • R
    Rachel FisherAug 25, 2025
    What to do if LG Control Unit damper doesn't completely close?
    • T
      Thomas ChapmanAug 25, 2025
      Inspect the damper linkage or hub of the LG Control Unit to ensure the damper can fully close.
  • B
    Brenda CarlsonAug 29, 2025
    Can I recalibrate the enthalpy sensor on my LG Control Unit?
    • J
      Joy RobertsAug 30, 2025
      The enthalpy sensor of the LG Control Unit cannot be recalibrated in the field. However, you can input a limited offset in temperature and humidity for each sensor connected to the economizer via a menu item under the ADVANCED menu.
  • M
    Michelle HuntSep 3, 2025
    Why is LG Control Unit outdoor temperature reading inaccurate?
    • W
      willie80Sep 3, 2025
      Verify the sensor wiring of your LG Control Unit. Ensure that enthalpy sensors are wired to the S-BUS terminals and temperature sensors are wired to the OAT and MAT terminals.