Operation
- 35 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
Temperature range by COMP SPEC varies by 10°C.
Portection from overheating of power module
Portection from overheating of compressor
T off °C
T2 °C
Heat Sink Temp.
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
T = (T off - T on)
T1 = T on + T
T2 = T on + 2
*
T
D-Pipe Temp.
COMP Freq. Free Free
Fh min
OFFFc-1 Fc-1Fc-2 Fc-2
T = (T off - T2)/2
T1 = T2 - 2
*
T
T3 = T2 + T
T off °C
T2 °C
T3 °C
T1 °C
-13 °C
1
AS-W096ERH0/BH0/VH0
85 95
2
AS-W126ERH0/BH0/VH0
85 95
No. MODEL T on T off
1
AS-W096ERH0/BH0/VH0
100 110
2
AS-W126ERH0/BH0/VH0
100 110
No. MODEL T on T off