54 Synchro Air Conditioner
Installation
2. AUUH728C/AUUH1008C
For additional charging method, see below table.
Note: If total additional charge value after calculation comes out to be negative, then do not consider additional
charge.
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
Synchro Refrigerant Additional charging (kg)
Duo
Refrigerant = (L1 - 5) x 0.05 + (L2 + L3 - 20) x A
Tr io
Refrigerant = (L1 - 5) x 0.05 + (L2 + L3 + L4 - 20) x A
Quartet
Refrigerant = (L1 - 5)
x
0.05 + (L2 + L3 + L4 + L5 - 20)
x
A
A
Refrigerant Branch
Pipe (mm)
Ø 6.35
Ø 9.52
0.03 kg/m
0.05 kg/m
(L1=Main Pipe, L2~L5 : Branch Pipe)
1. AUUH488C
There is not additional charging of refrigerant by main pipe of 30m below.
For additional charging method, see below table.
Note: If total additional charge value after calculation comes out to be negative, then do not consider additional
charge.
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
Synchro Refrigerant Additional charging (kg)
Duo
Refrigerant = (L1-30) x A + (L2+L3-20) x 0.03
Tr io
Refrigerant = (L1-30) x A + (L2+L3+L4-20) x 0.03
Quartet
Refrigerant = (L1-30)
x A +
(L2+L3+L4+L5-20)
x
0.03
Model
AUUH488C
A
0.07
(L1=Main Pipe, L2~L5 : Branch Pipe)
Refrigerant Additional Charging Method