4.6.2 Air guide work
In case of out door unit is located outdoor cabin of apart-
ment or flats, then the efficiency can drop and system
pressure increases thus finally damaging the compressor
or other components in the system by heat short circuit.
4.6.3 Lightning safety zone
1) To protect outdoor unit from lightning, it should be placed
within lightning safety zone.
Safety zone
2) Power cable and communication cable should be 4.9ft
away from lightning rod.
3) High resistance grounded system should be performed
against induced lightning or indirect stroke.
4) If the building has no lightning protection, outdoor may be
damage from lightning. This should be informed to cus-
tomer or building owner in advance.
Building Height [ft] 66 98 148 197
Protection Angle [˚] 55 45 35 25
n Where the obstacles on the discharge side is lower than the unit:
• No obstacle above
4) Series installation
• Obstacle above, too
ʻLʼ should be lower than ʻHʼ.
Close the bottom of the installation frame to prevent the
discharged air from being bypassed.