Service Manual 117
Troubleshooting Guide
Comp
Copper
pipe
Resistance() at 20°C
Resistance() at 20°C
0.64
0.64
0.64
Inverter
comp.
V-W
W-U
U-V
Terminal
0.8
0.8
0.8
Constant
comp.
2M
2M
2M
Inverter
comp.
V-GND
W-GND
U-GND
Terminal
2M
2M
2M
Constant
comp.
V
U
W
Comp
21
DC Peak
Instant over current
Over Rated current
Poor insulation of IPM
An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
- Pipe length.
Poor insulation of compressor
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Check the wire connection. (U,V,W)
2. Check the load condition. (Refrigerant, Pipe length, ) Adjust the load condition
3. Check the electricity leakage of the compressor. Normal : Over 2M.
4. Check the resistance of compressor. Normal : 0.65(INV), 0.8(Cons.) No difference at each terminal.
5. Check the insulation from water at IPM part. Check the trace of water.
6. Check the IPM circuit.
Troubleshooting CH21