58 Synchro Air Conditioner
Installation
Auto addressing
Auto addressing work should be done for simultaneous operation.
Addressing work assigns address to each Indoor Unit.
When firstly installing product or replacing the Indoor Unit PCB.
3. Auto Addressing Method
Table.a ZONE SW1 Setting 
TEST_SW1
LED01T
JIG_SW
1234
ZONE SW1
Main PCB
Fig.a Outdoor PCB diagram 
C
B
A
1. JIG_SW Setting  
Check the JIG_SW to the right, or not  set the JIG_SW to 
the right.( A )
2. ZONE SW1 Setting  
Set the ZONE SW1 as below Table.a ( B )
❈ S/W1 is not used.
❈ 1 means S/W up. 
0 means S/W down.
* Work procedure
1) Set JIG_SW and ZONE SW1 correctly.
2) Turn on main power. 
3) Press the TEST_SW1 for about 3 seconds within 3minutes After 
main power on.( C )
4) After step 3), the LED01T(green LED) rapidly flickers. 
When Addressing work is done, green LED is off, else LED stops 
flickering and lights continuously.
5) If you fail to perform the Addressing work,  
repeat step 2),3).
AUUH488C/AUUH728C/AUUH1008C
ZONE SW1
Indoor Unit No.
12
34
x0
00
x1
00
x
1
10
2(Duo)
1(Single)
3(Trio)
4(Quartet)
12
3
4
12
3
4
x
1
11
12
3
4