48 Synchro Air Conditioner
Installation
Outdoor Unit_AUUH1008C
1. Individual installation
Basic Space required
A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.
<Top View><Side View>
A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D : Front inlet(open in principle)
E : Rear inlet(open in principle)
D
C
B
A
E
service space
Front
Rear
A : 750 mm or more
B : 250 mm or more
When inlet air enters from right and left sides of unit
Rear
Front
A : 750 mm or more
B : 250 mm or more
C : 150 mm or more
<Top View> <Side View>
When unit is surrounded by walls
C
A
B
C
A
B
A
B
B
B