54 Synchro Air Conditioner
Installation
2. AUUH728C/AUUH1008C
For additional charging method, see below table.
❈ Note: If total additional charge value after calculation comes out to be negative, then do not consider additional
charge.
CAUTION: 
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of 
reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Synchro Refrigerant Additional charging (kg)
Duo
Refrigerant = (L1 - 5) x 0.05 + (L2 + L3 - 20) x A
Tr io
Refrigerant = (L1 - 5) x 0.05 + (L2 + L3 + L4 - 20) x A
Quartet
Refrigerant = (L1 - 5)
 x 
0.05 + (L2 + L3 + L4 + L5 - 20)
 x 
A
A
Refrigerant Branch 
Pipe (mm)
Ø 6.35
Ø 9.52
0.03 kg/m
0.05 kg/m
(L1=Main Pipe, L2~L5 : Branch Pipe)
1. AUUH488C
There is not additional charging of refrigerant  by main pipe of 30m below.
For additional charging method, see below table.
❈ Note: If total additional charge value after calculation comes out to be negative, then do not consider additional
charge.
CAUTION: 
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of 
reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Synchro Refrigerant Additional charging (kg)
Duo
Refrigerant = (L1-30) x A + (L2+L3-20) x 0.03
Tr io
Refrigerant = (L1-30) x A + (L2+L3+L4-20) x 0.03
Quartet
Refrigerant = (L1-30)
 x A + 
(L2+L3+L4+L5-20)
 x 
0.03
Model
AUUH488C
A
0.07
(L1=Main Pipe, L2~L5 : Branch Pipe)
Refrigerant Additional Charging Method