Service Manual 75
Operation
[Table. 1]
Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-
function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate
varies.
Static Pressure(mmAq)
Setting Value
Model Name
Step
CMM(CFM)
High 16.5(583) 235 230 225 215 180
18K Med 14.5(512) 245 238 235 230
215
Low 13(459) 254 252 248 245
240
High 18(636) 220 205 190 50
1
24K Med 16.5(583) 235 230 220 200
100
Low 14(494) 250 240 235 230
210
High 26.5(936) 153 150 150 148 130
1
30K Med 23(812) 173 173 175 175 170
155
Low 20(706) 190 190 190 190 190
190
High 32(1130) 230 230 225 220 150
1
36K Med 29(1024) 240 238 237 235 230
220
Low 26.5(936) 245 245 243 243 240
240
High 40(1412) 230 225 220 215 205 200 190 180
160
48K Med 35(1235) 250 245 240 235 230 220 215 210
200
Low 30(1059) 255 255 255 250 245 240 235 230
225
High 50(1766) 185 180 174 162 154 140 90 5 1
60K Med 45(1589) 210 205 199 191 189 180 155 138 110
Low 40(1423) 230 225 219 215 210 205 193 180
171
150 2 4 6 8 10 12 14