EasyManua.ls Logo

LG AUUC306A - Ceiling Concealed Duct Drain Piping Details

LG AUUC306A
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Service Manual 71
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A 70mm
B 2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A 70mm
B 40mm
C 20mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downware
inclination so water will drain out.
MAX 700mm
Drain Pipe
Drain Pump
1/50~1/1001/50~1/100
Front of view
Alway lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
CORRECT
Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.
The unit must be or declined to wards drain hose while installation.
CORRECT
INCORRECT
INCORRECT
Drain Piping of Ceiling Concealed Duct

Related product manuals