2. Installation Space
  5
MULTI/SINGLE CAC 
Installation of Outdoor Units
 Where there are obstacles on both suction and discharge sides:
 Where the obstacles on the discharge side is higher than the unit:
[Unit : mm(inch)]
The relations between H, A and L are as follows:
Close the bottom of the installation frame to prevent the discharged air from being bypassed.
 Where the obstacles on the discharge side is lower than the unit:
[Unit : mm(inch)]
• No obstacle above • Obstacle above, too
L A[mm(inch)]
L ˺ H
0 < L ˺ 1/2H
750(29 1/32)
1/2H < L 1 000(39 3/8)
H < L
Set the stand as: L ˺ H
• No obstacle above • Obstacle above, too
‘L’ should be lower than ‘H’.
Close the bottom of the installation frame to prevent 
the discharged air from being bypassed.
300(11-13/16)
    or more
500(19-11/16) or more
L
D
H
300(11-13/16)
  or more
L
S
H
1000(39-3/8) or more
1000(39-3/8) or more
500(19-11/16) or less
L
D
300(11 13/16)
or more
500(19-11/16)
or more
L
D
H
L
D
H
1000(39-3/8) or more
1000(39-3/8)
or more
500(19-11/16) or less
300(11-13/16)
or more