MULTI/SINGLE CAC 
4. Refrigerant piping system
10
Installation of Outdoor Units
 Single type - Synchro
CAUTION
 
• Please check the product type. Piping installation and refrigerant charge varies depending on the type of 
product.
For more information, please refer to the installation manual.
 
• When installing the branch pipe, direction and angle of installation is not limited.
• Take care so that burrs and foreign material may not enter into the cutting surface when connecting.
• Connect remaining those by cutting or direct insertion to the diameter of pipe.
 Refrigerant additional charge calculation method
Additional Refrigerant = (L1 - A) x a + (L2 + L3 + L4 + L5) x b
L1 (m) : Installed Branch Piping Length (Outdoor Unit ~ Branching Kit)
L2~L5 (m) : Installed Branch Piping Length (Branching Kit ~ Indoor Unit)
a (g/m) : Additional charging volume for Main Pipe (Outdoor Unit ~ Branching Kit)
b (g/m) : Additional charging volume for Branch Pipe (Branching Kit ~ Indoor Unit)
* Refer to the specifications for detail information of A, a.
* If total additional charge value after calculation comes out to be negative, then do not consider additional charge.
CAUTION
 
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
 
Liquid Pipe Diameter (mm) b (g/m)
Ø 6.35 35
Ø 9.52 40
Indoor Unit 
Indoor Unit 
Indoor Unit 
Indoor Unit
 
L1
 
L2 
L3 
L4
 
L5
 
L6
 
H2
 
H1
 
Branch
Notes
L1 (m) : Main Piping Length (Outdoor Unit ~ Branching Kit)
L2~L5 (m) : Branch Piping Length (Branching Kit ~ Indoor Unit)
L6 (m) : Length Difference (the Nearest Indoor Unit ~ the farthest Indoor Unit)
H1 (m) : Height Difference (Outdoor Unit ~ Indoor Unit)
H2 (m) : Height Difference (Indoor Unit ~ Indoor Unit)
Refer to the specifications of Outdoor Unit for Maximum limit.