Setting Value
Static Pressure(mmAq(Pa))
0 (0) 1 (10) 2 (20) 3 (30) 4 (40) 5 (50)
60 - - - - - -
65 5.03 - - - - -
70 5.60 4.85 - - - -
75 6.19 5.44 4.57 - - -
80 6.79 6.05 5.17 - - -
85 7.41 6.67 5.80 4.80 - -
90 8.05 7.31 6.43 5.44 - -
95 8.71 7.96 7.09 6.09 4.97 -
100 9.38 8.63 7.76 6.76 5.64 -
105 10.07 9.32 8.45 7.45 6.33 5.08
110 - 10.03 9.16 8.16 7.04 5.79
115 - - 9.88 8.88 7.76 6.51
120 - - - 9.62 8.50 7.25
125 - - - 10.38 9.26 8.01
130 - - - - 10.03 8.78
Setting Value
Static Pressure(mmAq(Pa))
0 (0) 1 (10) 2 (20) 3 (30) 4 (40) 5 (50)
75 6.50 - - - - -
80 7.34 6.70 - - - -
85 8.20 7.55 6.69 - - -
90 9.07 8.43 7.56 6.47 - -
95 9.96 9.32 8.45 7.36 - -
100 10.87 10.22 9.36 8.27 6.96 -
105 11.79 11.15 10.28 9.19 7.89 6.35
110 12.73 12.09 11.22 10.14 8.83 7.30
115 13.69 13.05 12.18 11.09 9.78 8.25
120 14.67 14.02 13.16 12.07 10.76 9.23
125 15.66 15.01 14.15 13.06 11.75 10.22
130 16.67 16.02 15.16 14.07 12.76 11.23
135 - - 16.18 15.10 13.79 12.26
140 - - - 16.14 14.83 13.30
145 - - - - 15.89 14.36
(Unit : CMM)
(Unit : CMM)
(Unit : CMM)
Setting Value
Static Pressure(mmAq(Pa))
0 (0) 1 (10) 2 (20) 3 (30) 4 (40) 5 (50)
85 10.19 - - - - -
90 12.18 10.71 11.09 - - -
95 13.81 12.34 12.19 - - -
100 15.16 13.69 13.38 10.71 - -
105 16.30 14.83 14.36 11.85 - -
110 17.31 15.85 15.23 12.86 10.97 -
115 18.27 16.80 16.07 13.82 11.93 -
120 19.26 17.79 16.93 14.80 12.91 10.49
125 20.34 18.87 17.89 15.88 13.99 11.57
130 21.60 20.13 19.01 17.14 15.25 12.83
135 - 21.64 20.36 18.66 16.76 14.35
140 - - 22.01 20.50 18.61 16.19
145 - - - 22.75 20.86 18.44
Note :
1. The above table shows the correlation between the air rates and E.S.P.