Table 1
ABNW18GM1A0, ABNW24GM1A0
ABNW30GM1A0
(Unit : CMM)
(Unit : CMM)
Setting value
Static Pressure (mmAq(Pa))
2.5(25) 4(39) 6(59) 8(78) 10(98) 12(118) 14(137) 15(147)
70 11.3
75 12.8
80 14.4 11.4
85 15.9 13.2 10.2
90 17.5 15.0 12.0
95 19.0 16.7 13.7 10.7
100 20.6 18.5 15.5 12.5
105 22.1 20.3 17.3 14.3 11.1
110 23.7 22.1 19.0 16.1 13.1 10.0
115 23.8 20.8 17.9 15.1 12.2
120 22.6 19.7 17.1 14.3 11.3
125 21.5 19.1 16.5 13.6 11.9
130 23.3 21.2 18.7 15.8 14.3
135 23.2 20.8 18.0 16.7
140 23.0 20.3 19.1
145 22.5 21.5
150 23.8
Setting value
Static Pressure (mmAq(Pa))
2.5(25) 4(39) 6(59) 8(78) 10(98) 12(118) 14(137) 15(147)
85 16.8 14.6
90 18.1 15.9
95 19.4 17.2 15.0
100 20.7 18.5 16.3 13.9
105 22.0 19.8 17.7 15.3 13.0
110 23.3 21.1 19.1 16.8 14.6
115 24.6 22.4 20.5 18.3 16.3 14.2
120 25.9 23.7 21.8 19.7 17.9 15.9 13.3
125 25.1 23.2 21.2 19.6 17.5 15.2 14.6
130 24.6 22.7 21.2 19.2 17.1 16.3
135 24.2 22.9 20.9 19.0 18.1
140 24.5 22.6 20.9 19.9
Note :