Part 4   Trouble Shooting 
- 126 -
Copyright © 2019 - 2020 LG Electronics Inc. 
All rights reserved. Only training and service purposes.
Purpose
Checking single units of sensors 
for fault
Items for checking
Measurement of the unique resistance by 
sensor temperature.
- Position : Outlet of 4-way valve (based on cooling mode)
ڻ Pressure sensor
After power supplied, 
the pressure on LGMV 
is normal before 
operating?
Voltage of 5V is output 
from the PCB?
The location and 
connection of connector 
is normal on PCB?
PCB checking and replacement 
Reconnection
Replace the pressure sensor
Checking start 
No malfunction of the pressure 
sensor
Yes
Yes
Yes
No
No
No
6.7 Troubleshooting Outdoor Error