3.1 E.S.P. (External Static Pressure) Setting
3. Installation Functions
Part 2   Functions & Controls
When pressing the        button and    
button simultaneously for more than 3 
seconds, the system will be entered into the 
installer setting mode.
- After entering into the installer setting 
mode, select the static pressure step 
setting code value by pressing the         
    button.
 
* Static pressure step setting code value : 32
1
Select the desired setting value with the
temperature up(
ƞ
), down(
Ơ
) button.
2
When pressing        button, currently 
established static pressure value will be set 
up.
3
When pressing the        button and   
button simultaneously for more than 3 
seconds after the setting has been 
completed, the setting mode will be 
released.
- If there isn’t any button input for more than 
25 seconds, the installer setting mode will 
also be released.
4
00: use static pressure (code 06) set value
01~ 11: static pressure step (code 32) set value
Function Code
Existing condition
This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some products.
This is the function that static pressure of the product is divided in 11 steps for setting.
Installer Setting - Static Pressure Step Setting
- Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32) setting is being
used.
- For the static pressure value for each step, refer to the next page.