LGE Internal Use Only
4. Test Run
Is cold air discharged for
more than 3 minutes ?
START
Test operation for indoor unit
Operation mode change
to Heating mode
Operate the unit in cooling mode.
Does Test operation start?
Refer to part4,  6 Electric part
Yes
No
Yes
Refer to part4,  5 Cycle part
No
Is hot air discharged ?
After Hot Start
Yes
No
Is there any temperature 
difference between intake and 
discharged air?  
Yes
No
Is the operating current 
normal ?
Yes
Normal
Refer to Troubleshooting 
Guide
No
* Check the load (In/Out Temp.)
* Check pipe length and amount of 
  refrigerant
* Check for abnormal sound in 
  outdoor unit (comp.,Fan, others ) 
2. Test Run Flow chart 
• Each indoor unit should be tested.
• If the unit has accessory, it should be tested.