EasyManua.ls Logo

LG FM30AH UE3 - Page 75

LG FM30AH UE3
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 74 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
5. Trouble Shooting
Check the resistance
0
CN Float
CN-Float
CN-D/PUMP
04
Drain pump
/ Float switch
Float switch Open.
(Normal : short)
The connection of wire(Drain pump/ Float switch)
Drain pump power input. (220V)
Drain tube installation.
Indoor unit installation. (Inclination)
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

Table of Contents

Related product manuals