Precautions to take during series installation
• Use a vacuum pump or Inert (nitrogen) gas when performing leak detection or air purge.
Do not use compressed air or oxygen, or inflammable gas. There is a risk of fire or explo-
sion.
There is a risk of death, injury, fire, or explosion.
WARNING
!
LEAK DETECTION
Leak detection should be made by pressurizing nitrogen gas to 3.8 MPa(38.7 kgf/cm
2
). Refer to
the diagram as follows. (Make a detection test with the service valve closed. Be sure to pressur-
ize the liquid pipe and the gas pipe.)
The test result can be judged good if the pressure has not been reduced for 24 hours after the
nitrogen gas pressurization.