EasyManua.ls Logo

LG GHP SUPER - Page 42

LG GHP SUPER
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
VACUUM AND REFRIGERANT CHARGE
ENGLISH
Refrigerant Charge
Gas pipe
Liquid pipe
• Pipe to be vacuumed: gas pipe, liquid pipe
• Do not charge with any other refrigerants than the designated refrigerant (R410A) when
transporting or reinstalling the unit.
• If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle
may malfunction causing damages.
WARNING
!
• Add exact amount of refrigerant calculated by the combination of the installation pipe
diameter length and the indoor unit.
• Incorrect amount of refrigerant may cause malfunction of the unit.
• If the additional amount of refrigerant exceeds the range of ±10%, the compressor burn-
ing or insufficient indoor unit performance may result.
Manifold gauge
Low pressure side handle
High pressure side handle
Refrigerant