ELECTRICAL WIRING
ENGLISH
47
5 Outdoor Unit Power Cable Specifications and Switch Capacity
• Make sure to use specified cables for connections so that no external force is imparted to
terminal connections. If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that the
generated overcurrent may include some amount of direct current.
The earth leakage circuit breaker should be installed. Otherwise, there is a risk of electric shock.
Do not use anything other than the breaker and the fuse with correct capacity.
Using the fuse, cable, or cooper wire with too large capacity may cause a malfunction or fire.
• Be sure not to make the 3-phase 4-wire system of the indoor unit connection as a
reversed phase or open phase when connecting.
• Use round pressure terminals for connections to the power cable. It may cause fire or
flame damages on the electrical parts.
When installing the main power, make sure to have N phase. If the voltage of R.S.T. phase is
impressed in the “N” phase, it causes fire damage on the valuable electric components.
WARNING
!
Type of
Outdoor
Unit
Power
Specifications
Wire Thickness (mm
2
)
Earth Leakage
Circuit Breaker
(ELCB)
Main power
cable wire
Branch wire Ground wire
1Unit
3 Ø, 380 V3N~, 60 Hz 2.5 - 2.5 30A
1 Ø, 220 V~, 60 Hz 2.5 - 2.5 30A
2Unit
3 Ø, 380 V3N~, 60 Hz 4.0 - 2.5 ~ 4.0 60A
1 Ø, 220 V~, 60 Hz 6.0 - 2.5 ~ 6.0 60A
Branch wire
Power cable wire between a master and a slave1 outdoor unit — minimum of 2.5 mm²
h The above standards are based on CV wires.
h For detailed wire specifications, contact the head office.
h For 3-phase products, use 3-phase, 4-wire and 4-pole ELCB.
h For single-phase products, use 2-pole or 3-pole ELCB.
- Do not install any 'individual switch or electrical outlet' to disconnect each of indoor unit sepa-
rately from the power supply.
- Bear in mind the ambient conditions (ambient temperature, direct sunlight, rain water, etc.)
when proceeding with the wiring and connections.
- The cable size is the minimum value for metal conduit wiring.
The power cable size should be 1 rank thicker than normal, taking into account the cable voltage
drops.
- For the specific wiring work, comply with the requirements of the wiring regulations of the
region.
- For the power cable of the outdoor unit parts, use a standardized products.
- Do not connect the ground wire to any gas pipes, liquid pipes, lightening rod or telephone
ground wire.
- Make sure to use the leakage circuit breaker.