ADDITIONAL FUNCTIONS
ENGLISH
59
CAUTION
• Ask the licensed installer for the function setup when installing the outdoor unit.
• Set it OFF if you do not use the function.
!
Static pressure compensation mode
Lift the dip switch #5 up to set up the additional functions as you desire by using the buttons.
This function secures the air flow rate of outdoor unit, in case static pressure has been applied
like using duct at fan discharge of the outdoor unit.
Mode Setup
Fan Rotation Setup
Dip switch #5 of the outdoor unit ON
Display "Func" on 7-segment using '▶', and
'◀' buttons, and press the '●' button.
Display "Fu2" on 7-segment using '▶', and
'◀' buttons, and press the '●' button.
Display either "OFF", "op1', or "op2" on
7-segment using '▶', and '◀' buttons, and
press the '●' button.
Operate it at the set RPM
Volume
3Phase 380V 50Hz 1Phase 220V 50Hz
Cooling MAX. fan
RPM
Heating MAX. fan
RPM
Cooling MAX. fan
RPM
Heating MAX. fan
RPM
oFF 950 950
920 920
op1 1000 1000
op2 1020 1000
op3 1050 1000