Possible Trouble 2 The compressor does not operate.
Possible Trouble 3 The compressor always operate.
Is desired
Temp. set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
Replace IC01M.
Select the desired Temp. to lower Number.
Wait 3 Minutes.
Is the Unit for 3 minutes
delay?
Replace AC
PCB Ass'y.
Is the voltage N0.9 of
IC01M DC 12V?
Check the RY-COMP.
Check the wiring
Diagram.
NO
NO
NO
YES
YES
YES
YES
Is the wire connection of
RY-COMP OK?
Check the RY-COMP.
Connect LEAD Wire to
RY-COMP again.
NO
YES
NO
32 Room Air Conditioner