TROUBLESHOOTING
Error Codes
Refer to Service Manuals posted on www.lghvac.com for a full description of all error codes and work-arounds.
Error
Code
Description
No. of Times Outdoor Unit
LEDs Blink
LED1
(Plasma LED)
LED2
(Power LED)
61 Outdoor unit condenser coil temperature is too high 6X 1X
62 Outdoor unit inverter compressor PCB heat sink temperature is too high 6X 2X
63 Condenser coil pipe thermistor temperature is too low 6X 3X
65 Heat sink thermistor has disconnected or has shorted out 6X 5X
67 Outdoor brushless direct current (BLDC) fan motor lock error 6X 7X
Table 22: Table 33: Single Zone Wall Mounted Outdoor Unit Error Codes - Continued