Installation Manual 21
ENGLISH
Put a couple drops of refrigerant oil on the
face of the flare before assembling taking
care not to add any contaminants.
Align the center of the pipings and
sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
mm inch kgf.cm
Ø6.35 1/4 180~250
Ø9.52 3/8 340~420
Ø12.7 1/2 550~660
Ø15.88 5/8 630~820
Ø19.05 3/4 980~1210
Outside diameter Torque
Outdoor unit
Liquid side piping
(Smaller diameter)
Gas side
piping
(Bigger
diameter)
Torque wrench
Installation
Connecting the PipingConnection Of Piping -Outdoor