2. Ceiling dimension and hanging
bolt location
Installation of Unit
Install the unit above the ceiling correctly.
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
23
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
A
B
C
1-3 mm
D
(G)
H
I
EF
A B C D E F (G) H I
18K BTU/h
942 880 466 54 575 30 87 750 186
24K BTU/h
942 880 466 54 575 30 87 750 186
30K BTU/h
1242 1180 492 54 600 30 87 830 186
1242 1180 492 54 600 30 87 830 186
1242 1180 492 54 600 30 87 830 186
1292 1230 570.5 54 680 30 120 1006 294
1292 1230 570.5 54 680 30 120 1006 294
Dimension
Capacity
36K BTU/h
(LB-F36)
42K BTU/h
48K BTU/h
(LB-E48)
60K BTU/h
(LB-E60)
NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.