- 38 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
When compressor does not operate normally.
n Communication error between Indoor and Outdoor (Error Code )
Trouble 5-1
Is the LCD of wired remote controller
shows 'CH05'?
Check the state of connecting cable
(4 line) bewteen indoor and outdoor unit .
NO
YES
Is the connecting state of connector
outdoor PCB Ass'y right?
• Electrical wiring diagram(Colors)
• Check the connecting state
of connectors in outdoor PCB Ass'y
(CN_Data - Terminal Block.)
NO
YES
Is the connection of CN-DATA between
indoor and outdoor unit right?
Replace the PCB Ass'y.
• Main PCB Ass'y (Indoor/Outdoor)
• Reconnect the cable to terminal block.
• Check the PCB pattern(Resoldering).
NO
YES